Krangard Group
Loading the next chapter…
Krangard Group
Loading the next chapter…
06 / Monobloc Heat Pumps
Wall-mounted single-package R32 heat pump with no outdoor unit or line set; 7,080 to 11,800 Btu/h cooling in two sizes.


Image 1 of 1
The wall monobloc is a single-package heat pump mounted on the inside of an exterior wall. Every refrigerant component is indoors, so there is no outdoor unit, no line set and no condensing unit.
Two sizes are published: size 25 on a 115 V supply and size 40 on a 208 V supply, with rated cooling of 7,080 and 11,800 Btu/h and heat-pump heating of 7,120 and 10,900 Btu/h. Electric heaters from 600 W to 3,000 W are available by size.
The wall monobloc shares its wall-mounted housing, R32 refrigerant and controls with the cold-climate and water-source versions.
Climate and performance notes
Low-temperature heat-pump data for this line is listed as available on request; it is not one of the three lines with published data down to −5 °F.
| Sizes | 25 and 40 |
|---|---|
| Supply | Size 25: 115 V / 60 Hz. Size 40: 208 V / 60 Hz |
| Cooling | Size 25: 7,080 Btu/h (2.07 kW). Size 40: 11,800 Btu/h (3.46 kW) |
| Heating, heat pump | Size 25: 7,120 Btu/h (2.09 kW). Size 40: 10,900 Btu/h (3.19 kW) |
| Electric heater | Size 25: 600 or 1,000 W. Size 40: 1,400, 2,000 or 3,000 W |
| EER / COP | Size 25: 8.37 Btu/W / 2.97. Size 40: 9.76 Btu/W / 3.37 |
| SEER2 / HSPF2 | Size 25: 13.85 / 7.75. Size 40: 15.55 / 8.2 |
| Size and weight | Size 25: 935 × 543 × 198 mm; 39.0 kg. Size 40: 1000 × 580 × 218 mm; 53.1 kg |
| Refrigerant | R32 |
| Fan speeds | Three, with auto |
| Set-point range | 64.4 to 86 °F (18 to 30 °C) |
| Low-temperature data | On request |
| Electric heater | 600 or 1,000 W (size 25); 1,400, 2,000 or 3,000 W (size 40) |
|---|---|
| Control | Built-in touch panel with remote; optional 24 V wall thermostat |
| Versions in the same housing | Wall monobloc, cold-climate monobloc, water-source monobloc |
| Standard or mark | Status |
|---|---|
| CSA C22.2 No. 60335-2-40 (electrical safety; cCSAus, cULus or cETLus mark) | Specified to standard |
| CSA B52 Mechanical Refrigeration Code (A2L refrigerants) | Specified to standard |
| ISPM 15 (wood packaging entering Canada) | Specified to standard |
Status reflects Krangard Supply product literature (krangard-supply-06-hvac_2026). Certification is confirmed model by model: the current certificate, listing or test report for the specified model is issued with the project submittal. Code compliance for a building is determined by the project's design professionals and the authority having jurisdiction.
HVAC Systems brochure, pages 4, 6, 10
Applicable data sheets, test evidence, shop drawings and certification documents are coordinated for the selected model. Availability and any outstanding requirements are confirmed during the project review.

Monobloc Heat Pumps
Wall monobloc heat pump with published heating capacity and COP at 47, 10, 5 and −5 °F; no outdoor unit. Available from January 2027.
Specifications

Monobloc Heat Pumps
Wall monobloc heat pump connected to a building water loop instead of outdoor air; 8,500 to 12,100 Btu/h cooling, COP 5.2 to 5.5.
Specifications

Monobloc Heat Pumps
Monobloc heat pump with a 160 mm (6.3 in) deep cabinet, in inverter, hybrid and air-purifying versions; R32.
Specifications
Next step
Send your drawings or product schedule. We will review the requirements and confirm the next steps for pricing, documentation and samples.