Krangard Group
Loading the next chapter…
Krangard Group
Loading the next chapter…
06 / Monobloc Heat Pumps
Floor-standing monobloc heat pump for narrow floor space, recessed or ducted; 8,500 to 13,600 Btu/h in three cabinets; R32.


Image 1 of 1
The floor-standing monobloc is the format for narrow floor space and for recessed or ducted installation. It supplies air from the top or the front, ductless or ducted, and takes an optional fresh-air kit.
Three cabinets are published on a 208 V / 60 Hz supply. The compact and compact-tall units are 490 mm wide and 185 mm deep and deliver 8,500 Btu/h cooling; the large unit is 702 mm wide and delivers 13,600 Btu/h cooling and heating.
Climate and performance notes
Low-temperature heat-pump data for this line is listed as available on request; it is not one of the three lines with published data down to −5 °F.
| Models | Compact; Compact, tall; Large |
|---|---|
| Supply | 208 V / 60 Hz (all models) |
| Cooling | Compact and Compact, tall: 8,500 Btu/h (2.5 kW). Large: 13,600 Btu/h (3.98 kW) |
| Heating, heat pump | Compact and Compact, tall: 7,800 Btu/h (2.28 kW). Large: 13,600 Btu/h (3.98 kW) |
| Electric heater | Compact and Compact, tall: 2,000 W. Large: 1,500, 2,000 or 3,000 W |
| EER / COP | Compact and Compact, tall: 9.8 Btu/W / 3.16. Large: 9.6 Btu/W / 3.2 |
| Size W × H × D | Compact: 490 × 1544 × 185 mm. Compact, tall: 490 × 1664 × 185 mm. Large: 702 × 1912 × 305 mm |
| Weight | Compact: 61.2 kg (135 lb). Compact, tall: 62.1 kg (137 lb). Large: 90.7 kg (200 lb) |
| Refrigerant | R32 |
| Low-temperature data | On request |
| Air supply | Top or front; ductless or ducted |
|---|---|
| Fresh air | Optional fresh-air kit |
| Electric heater, large model | 1,500, 2,000 or 3,000 W |
| Standard or mark | Status |
|---|---|
| CSA C22.2 No. 60335-2-40 (electrical safety; cCSAus, cULus or cETLus mark) | Specified to standard |
| CSA B52 Mechanical Refrigeration Code (A2L refrigerants) | Specified to standard |
| ISPM 15 (wood packaging entering Canada) | Specified to standard |
Status reflects Krangard Supply product literature (krangard-supply-06-hvac_2026). Certification is confirmed model by model: the current certificate, listing or test report for the specified model is issued with the project submittal. Code compliance for a building is determined by the project's design professionals and the authority having jurisdiction.
HVAC Systems brochure, pages 4, 7, 10
Applicable data sheets, test evidence, shop drawings and certification documents are coordinated for the selected model. Availability and any outstanding requirements are confirmed during the project review.

Monobloc Heat Pumps
Wall-mounted single-package R32 heat pump with no outdoor unit or line set; 7,080 to 11,800 Btu/h cooling in two sizes.
Specifications

Monobloc Heat Pumps
Wall monobloc heat pump with published heating capacity and COP at 47, 10, 5 and −5 °F; no outdoor unit. Available from January 2027.
Specifications

Monobloc Heat Pumps
Wall monobloc heat pump connected to a building water loop instead of outdoor air; 8,500 to 12,100 Btu/h cooling, COP 5.2 to 5.5.
Specifications
Next step
Send your drawings or product schedule. We will review the requirements and confirm the next steps for pricing, documentation and samples.