06 / Packaged Terminal Heat Pumps
Wall-sleeve PTHP with a 185 mm deep room-side section and heat-pump data published to −5 °F; 9,300 to 14,500 Btu/h; R454B.


Image 1 of 1
The slim PTHP is a packaged terminal heat pump in a wall sleeve for hotels and multi-unit residential buildings, new or replacement. The room-side section is 185 mm deep and the unit suits walls from 229 mm (9 in) thick.
Three sizes are published on a 208 V / 60 Hz single-phase supply, with cooling of 9,300, 12,500 and 14,500 Btu/h at 95 °F and heat-pump heating of 9,000, 12,000 and 14,000 Btu/h at 47 °F. The outdoor operating range is −5 to 113 °F.
Heating capacity and COP are published at 47, 10, 5 and −5 °F. At −5 °F the three sizes retain 62 to 66 per cent of rated heat-pump capacity at a COP of 1.70 to 1.85, and each carries a 2,000 W electric heater.
Climate and performance notes
Heat-pump heating is published down to −5 °F (−20.6 °C); the outdoor operating range is −5 to 113 °F. At −5 °F the unit retains 62 to 66 per cent of rated heat-pump capacity at a COP of 1.70 to 1.85, with a 2,000 W electric heater for supplemental heating. Selection must be checked against the room's design heating load.
| Sizes | 09, 12 and 14 |
|---|---|
| Supply | 208 V / 60 Hz, single phase |
| Outdoor range | −5 to 113 °F (all sizes) |
| Cooling at 95 °F | Size 09: 9,300 Btu/h; EER 11.3. Size 12: 12,500 Btu/h; EER 11.1. Size 14: 14,500 Btu/h; EER 10.6 |
| Heating at 47 °F | Size 09: 9,000 Btu/h; COP 3.45. Size 12: 12,000 Btu/h; COP 3.40. Size 14: 14,000 Btu/h; COP 3.30 |
| Heating at 10 °F | Size 09: 6,980 Btu/h; COP 2.15. Size 12: 9,300 Btu/h; COP 2.05. Size 14: 11,600 Btu/h; COP 2.03 |
| Heating at 5 °F | Size 09: 6,600 Btu/h; COP 2.01. Size 12: 8,800 Btu/h; COP 1.95. Size 14: 11,000 Btu/h; COP 1.93 |
| Heating at −5 °F | Size 09: 5,600 Btu/h; COP 1.85. Size 12: 7,500 Btu/h; COP 1.70. Size 14: 9,300 Btu/h; COP 1.73 |
| Heating at −5 °F compared with rated | Size 09: 2.64 kW rated, 1.64 kW, 62 %. Size 12: 3.52 kW rated, 2.20 kW, 62 %. Size 14: 4.10 kW rated, 2.73 kW, 66 % |
| Electric heater | 2,000 W (all sizes) |
| Net weight | Size 09: 59.0 kg (130 lb). Size 12: 65.8 kg (145 lb). Size 14: 68.0 kg (150 lb) |
| Room-side section | 1168 × 450 × 185 mm |
| In-sleeve section | 1041 × 366 × 229 to 274 mm |
| Wall thickness | From 229 mm (9 in) |
| Refrigerant | R454B |
| Options | Energy-recovery fresh-air kit, anti-corrosion coating and Wi-Fi |
|---|---|
| Control | Built-in touch panel with remote; optional 24 V wall thermostat |
| Standard or mark | Status |
|---|---|
| CSA C22.2 No. 60335-2-40 (electrical safety; cCSAus, cULus or cETLus mark) | Specified to standard |
| CSA B52 Mechanical Refrigeration Code (A2L refrigerants) | Specified to standard |
| CSA C744 / AHRI 310/380 (packaged terminal unit performance) | Specified to standard |
| ISPM 15 (wood packaging entering Canada) | Specified to standard |
Status reflects Krangard Supply product literature (krangard-supply-06-hvac_2026). Certification is confirmed model by model: the current certificate, listing or test report for the specified model is issued with the project submittal. Code compliance for a building is determined by the project's design professionals and the authority having jurisdiction.
HVAC Systems brochure, pages 4, 5, 8, 10
Applicable data sheets, test evidence, shop drawings and certification documents are coordinated for the selected model. Availability and any outstanding requirements are confirmed during the project review.

Monobloc Heat Pumps
Wall-mounted single-package R32 heat pump with no outdoor unit or line set; 7,080 to 11,800 Btu/h cooling in two sizes.
Specifications

Monobloc Heat Pumps
Wall monobloc heat pump with published heating capacity and COP at 47, 10, 5 and −5 °F; no outdoor unit. Available from January 2027.
Specifications

Monobloc Heat Pumps
Wall monobloc heat pump connected to a building water loop instead of outdoor air; 8,500 to 12,100 Btu/h cooling, COP 5.2 to 5.5.
Specifications
Next step
Send your drawings or product schedule. We will review the requirements and confirm the next steps for pricing, documentation and samples.